EL3314-0002
Click image for Gallery
4-channel thermocouple input terminal, preset to type K, with wire breakage detection, 24 bit, high-precision, electrically isolated
Information | |
About product | The EL3314-0002 analog input terminal allows the direct 2-wire connection of four thermocouples. The channels are electrically isolated from one another and from the E-bus, thus preventing interference and damage due to cross-currents. Various types of thermocouple are supported; the voltage is calculated in temperature directly in the terminal. The terminal can also be used for mV measurements. A broken wire is signalled by the error LEDs and on the fieldbus. Cold junction compensation takes place by means of precise internal temperature measurement at the connecting terminals, but operation with an external cold junction is also possible. |
I/O attributes | |
Bus type | E-bus |
I/O type | Ai |
Signal Type | Thermocouple |
Number of channels | 4 |
Filter | Typ. 1 kHz |
Special features / functions | Open-circuit recognition |
DC, XFC, Oversampling | No |
Intrinsically safe (Ex i) | No |
Safety (Sil3 / Cat. 4, PL e, SC) | No |
Temperature range | 0…+55 °C |
Connection technology | 2-wire |
IP class | Ip20 |