1-channel thermocouple input terminal, preset to type K, with wire breakage detection, 16 bit
Information | |
About product | The EL3311 analog input terminal allows thermocouples to be connected directly. The EtherCAT Terminal's circuit can operate thermocouple sensors using the 2-wire technique. Linearisation over the full temperature range is realised with the aid of a microprocessor. The temperature range can be selected freely. The error LEDs indicate a broken wire. Compensation for the cold junction is made through an internal temperature measurement at the terminal. The EL3311 can also be used for mV measurement. |
I/O attributes | |
Bus type | E-bus |
I/O type | Ai |
Signal Type | Thermocouple |
Number of channels | 1 |
Filter | Typ. 1 kHz |
Special features / functions | Open-circuit recognition |
DC, XFC, Oversampling | No |
Intrinsically safe (Ex i) | No |
Safety (Sil3 / Cat. 4, PL e, SC) | No |
Temperature range | -25°...60°C |
Connection technology | 2-wire |
IP class | Ip20 |